Phase one: what happened
24 October 2026
The public inquiry that Theresa May promised the Commons eight days after the fire took its evidence in two stages, and the first stage answered the narrowest and hardest question: what, exactly, happened on the night of 14 June 2017. The Phase 1 report, published in October 2019 under the inquiry's chairman, the retired Court of Appeal judge Sir Martin Moore-Bick, runs to an overview and four volumes. Its method was forensic: a detailed narrative of the night organised into eleven separate periods between 00.54, shortly before the control room received the first call, and 08.10, when the last survivor left the tower, built from the evidence of survivors and firefighters, the recordings of the emergency calls and the testimony of expert witnesses. A fifth part carried the chairman's recommendations for change following the fire, some of them directed at the London Fire Brigade itself. PM Commons statement on Grenfell Tower: 22 June 2017 - GOV.UK Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30) Publication of the Grenfell Tower Inquiry Phase 2 report - GOV.UK publications page
On the origin of the fire the report is exact, and it is careful to be exact about one thing more. The fire was started by an electrical fault in a large fridge freezer in the kitchen of Flat 16, a finding the chairman delivers with a rider that matters to everyone who ever repeated the address: Behailu Kebede, the flat's tenant, bears no blame. The precise nature of the fault could not be established, and the report treats that as the less important question; what mattered was what the fire found once it left the kitchen. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Its central engineering finding was that the tower's compartmentation, the sealed box principle on which the whole high rise fire safety doctrine rests, was lost at an early stage, and it said precisely how. First, the intensity of the heat was such that the glass in the windows inevitably failed, allowing the fire to penetrate flats. Second, extractor fan units in the kitchens had a propensity to deform and become dislodged, providing a point of entry. Third, key fire protection measures inside the tower failed: although some fire doors held back the smoke, others did not, because some lacked effective self closing devices and failed to close, while others were broken down by firefighters or wedged open with firefighting equipment as crews fought their way in. The doors became a finding of their own. In her supplemental report the inquiry's expert Dr Lane drew attention to serious questions about the fire doors throughout the tower, both the entrance doors to individual flats opening into the lobbies and the doors opening from the lobbies into the stairs. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Quietest and bleakest of the report's tables is the smoke timeline. Many lobbies had begun to fill with smoke by around 01.20; by 01.40 some were significantly smoke logged, and by 02.00 a significant number were heavily smoke logged. Until around 01.50 there was less smoke in the stairs; after that time they began to fill, particularly at lower levels, and by 02.20 the smoke in them posed a risk to life. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
On the precise route out of Flat 16 the report is more tentative but no less specific. Its best judgment is that the fire escaped through the window: hot smoke impinging on the uPVC window jamb, deforming and collapsing it, opening a path into the cavity between the insulation and the ACM panels through which flames and hot gases could pass. The alternative, rated possible but less likely, was flame passing straight through the open kitchen window onto the panels above. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Two more of its findings shrink the margin for hindsight. By the time firefighters opened the kitchen door in Flat 16 for the first time, at 01.14, the fire had already entered the cladding; and a kitchen fire of that relatively modest size, the report notes, was perfectly foreseeable. Once out of the flat, the fire ran up the east face and then around the top of the building in both directions, and the report apportions the routes with an engineer's precision: the crown was primarily responsible for the spread of the fire horizontally, the columns were a principal route of downward spread, and the polyisocyanurate and phenolic foam insulation boards behind the panels, and perhaps components of the window surrounds, contributed to the rate and extent of the vertical flame spread. Nothing about the physics required anything unusual to happen in Flat 16. The wall was the accelerant waiting for an ordinary fire. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Fuel, too, had a name in the report. In the finding on which everything since has turned, it concluded that the principal reason the flames spread so rapidly up, down and around the building was the presence of the aluminium composite material rainscreen panels with polyethylene cores, and that the principal mechanism for the fire's horizontal and downward spread was the melting and dripping of burning polyethylene from the crown and the spandrel and column panels, which set fires lower down that then travelled back up the building. Hot smoke impinging on the cladding had carried the fire out of Flat 16 and up the east facade; the architecture of the refurbished wall did the rest. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
And the report put the building itself on the wrong side of the law that then stood. There was, the chairman found, compelling evidence that the external walls failed to comply with Requirement B4(1) of the Building Regulations 2010, in that they did not adequately resist the spread of fire having regard to the tower's height, use and position. On the contrary, they actively promoted it. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Readiness took its own indictment. Incident commanders and senior officers attending the fire had received no training in the particular dangers associated with combustible cladding, even though some senior officers were aware of similar fires in other countries, and of the fact that construction materials and methods were changing. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Its recommendations reached past the tower into every high rise: premises information boxes, regular inspection and testing of lifts designed for use by firefighters, marking of floor levels in lobbies and staircase landings, inspection of fire doors and self closing devices, and closer co operation between the emergency services. It reached further, into the toolbox itself: the provision of equipment enabling firefighters to send an evacuation signal to the whole or a selected part of a building under attack, and the requirement that every fire and rescue service be equipped to receive and store electronic plans and make them available to incident commanders and control room managers in the middle of the night. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
One suggestion put to the chairman by certain core participants went beyond anything the report adopted: that no materials be permitted for use in the external walls of high rise buildings unless they met Euro class A1, the highest classification of reaction to fire. On that, the report recorded simply that views differ, and that the government had already consulted. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)
Two questions the first report left open were settled later, and settled by fire. In experiments designed by Professor Bisby and Professor Torero and carried out at Edinburgh University by Professor Bisby and his colleagues, the ACM panels were shown to have been by far the largest potential contributor to energy release in the tower's external wall system; the two insulation foams, Celotex's polyisocyanurate RS5000 and Kingspan's phenolic K15, both had a much lower heat release rate per unit area. A cavity on its own, the experiments showed, is not sufficient to make a fire in rainscreen panels develop to full involvement: insulation must be present too, to hold energy within the system or to burn and contribute more, and even non combustible mineral wool produced the growth of the fire to full involvement of the panel; panels fixed in cassette form behaved far worse than panels in riveted form. The experimental work confirms that the principal factor in the rapid growth of the fire was the unmodified polyethylene in the cores of the panels rather than the insulation, though the insulation's ability to retain heat was a decisive factor in promoting that growth. Grenfell Tower Inquiry: Phase 2 Report Overview (2024-09-04)
Phase 1 deliberately did not assign the deeper blame. The report itself says so in its own structure: an examination of the relevant building regulations and the guidance published by the government in support of them, it notes, would form an important part of the inquiry's later work. The questions of how the tower came to be wrapped in that material, who knew what about its behaviour, which rules failed and whose decisions let it happen were reserved for the inquiry's second phase. The first report's catalogue of one night's failures, exact down to the minute and the door, stood from October 2019 as the agreed floor of fact beneath everything still in dispute. Grenfell Tower Inquiry: Phase 1 Report Overview (2019-10-30)