Four safeguards, none switched on
Published 15 October 2026
A good deal of what follows depends on one uncomfortable comparison. An Institution of Chemical Engineers article based on Carbide's March 1985 report, describes a plant that was designed with many safety features, and then lists, in its own event table, how many of them had stopped working by the end of 1984. The article presents the account based on Carbide's report. [33]
The design first. The MIC tanks were built from type 304 stainless steel and covered with a concrete deck. The MIC was meant to be held at around 0 degrees Celsius, circulated through heat exchangers cooled by a 30 ton refrigeration plant that ran on a nonaqueous coolant, because water was deliberately kept out of the system in case of a leak. Each tank carried a temperature indicator and alarm, a pressure controller, a level indicator, and safety valves set at 3.8 bar with rupture discs. [33]
Behind the tanks stood the last line of defence. The vent gas scrubber was a packed tower 1.7 metres across and 18 metres tall, circulating caustic soda to neutralise any MIC vented from the tanks. Next to it stood a flare tower that could burn off whatever the scrubber let through, fitted with a seal tank so it could not backfire. On paper, a tank that overheated would vent into the scrubber, and anything that survived the scrubber would burn at the flare. [33]
Now the event table. In June 1984, according to the company's own report, the refrigeration plant for the MIC tanks was shut down, so storage temperature drifted between about 15 and 20 degrees Celsius from June to December. The same entry says the temperature alarm was disconnected and not reset to a higher setting, so no automatic warning would come from a rising temperature. The IChemE article adds, with what reads like deliberate understatement, that its own Institute plant in West Virginia never lets the MIC temperature exceed 5 degrees. [33]
On 23 October, when MIC production stopped, the scrubber's circulation pump was set to standby. The table notes that there was no automatic start for the caustic circulation and that it could only be started by hand. The flare stack was out of service for maintenance, and The IChemE article admits that the date maintenance began is unknown. The report's own summary says that over the period from June until the incident many of the safety features had been rendered inoperative, without anyone recognising that a hazard remained even though MIC production had been discontinued. [33]
That leaves a conclusion the IChemE article drew: the incident reached the proportions it did because of the incremental degradation of previously well designed safety measures. It is a fair sentence, and it cuts both ways. It credits the design and blames the decay, and the decay happened in a plant that Carbide's Indian subsidiary ran under Carbide's technical collaboration. [33]
Indian scientists took a harsher view of the design itself. The CSIR team, which the trial court says was headed by CSIR Director General S. Varadarajan, argued in December 1985 that the factors behind the leak lay in the unique combination of MIC's properties and the features of the plant. MIC is highly reactive, volatile enough to become a gas, and very toxic when inhaled. Storing large quantities of it for long periods in single large tanks was made possible by the facilities installed, and the report says there was insufficient caution in design, in the choice of materials and in instruments, together with no facilities for quickly and safely disposing of material showing instability. [6] [8]
Its technical findings began with the route into storage. There were no facilities to collect each shift's MIC separately and no on line analysers, so MIC went straight to storage without batch wise analysis. Nitrogen came from a neighbouring factory and was fed into the tanks without intermediate storage or quality checks. Carbon steel sections were used in the connectors to the storage tanks and copper tubes in the connectors to the level instruments, in a plant handling a chemical that reacts violently with traces of metals. The alarm instruments for sudden temperature increase were, in the report's words, not suited to the conditions of operation. Only a single refrigeration system served both tanks, and it had not been operated for a considerable time. [8]
The same document puts a number on the scrubber's performance. When the CSIR team examined it, they found the installed disposal facilities incapable of meeting their objective within the very short time of two hours that a runaway reaction would allow. So the last line of defence was not simply switched to standby. Even switched on, in the report's assessment, it could not have done the job in the time available. [8]
At the criminal trial the defence told a different story, and it deserves to be heard in its strongest form. V.K. Behl, who had been safety manager at UCIL Bhopal from August 1978 to May 1984, testified that a very high standard of security was maintained and that there were several safety manuals for the plant. The magistrate was unimpressed: Behl said nothing about the design of the plant, and the manuals were all in English, a language that less qualified workers might not understand. A second defence witness, N.C. Agnihotri, said the Bhopal plant was built on the same pattern as the Virginia one, only half the capacity. The court answered that India's team of scientists had never been allowed to visit the Virginia plant and that the defence produced no brochure or document showing the two were alike. [6]